Wire Size Calculator
Work out the smallest wire that safely carries your load — by the NEC Table 310.16 ampacity, with the ambient and bundling derating and the 60 °C terminal limit applied the way the code applies them. Most simple calculators skip the terminal rule and undersize the wire; this one does not. The result is an estimate for planning — always have a licensed electrician check the final sizing.
Calculate your wire size
The 125% rule: a load that runs 3 hours or more must be sized as if it drew 25% more current (NEC 210.19(A)(1)). The terminal limit: on circuits up to 100 A the wire is also limited by the 60 °C column, because most breakers and devices are only rated 60 °C at the terminals (NEC 110.14(C)). That is why a 20 A continuous load needs 10 AWG, not 12 AWG.
Your results
How the wire size formula works
Wire sizing is three checks in a row: the load with the continuous-load rule, the ampacity with derating, and the voltage drop over the run.
Required ampacity: load × 1.25 if continuous, else load — NEC 210.19(A)(1)
Derated ampacity: NEC 310.16 value × ambient factor × bundling factor — NEC 310.15(B)(1) and 310.15(C)(1)
Terminal limit: allowed = min(derated ampacity, 60 °C column value) on circuits up to 100 A — NEC 110.14(C)
Voltage drop: VD = 2 × L × I × R ÷ 1000 (single-phase) or VD = √3 × L × I × R ÷ 1000 (three-phase) — resistance from NEC Chapter 9 Table 8
Breaker: next standard size at or above the required ampacity — NEC 240.6(A); 14 AWG is capped at 15 A, 12 AWG at 20 A, 10 AWG at 30 A (NEC 240.4(D))
This uses the standard method, verified against published examples: 12 AWG copper at 90 °C is 30 A in the table, but with 60 °C terminals the allowed ampacity is 20 A — which is why a 20 A continuous load (25 A required) needs 10 AWG, not 12 AWG. The one judgement call is the terminal rating: this calculator assumes 60 °C terminals up to 100 A, the common case for residential breakers and devices. If your equipment is marked 75 °C, the 75 °C column governs and one size smaller may pass — check the markings on the breaker and the device.
Worked example
A 30 A continuous load, 240 V, single-phase, 100 ft run, copper, 75 °C insulation, 30 °C ambient, 1–3 conductors, 10% spare wire:
Required: 30 × 1.25 = 37.5 A
10 AWG: 35 A × 1.00 × 1.00 = 35 A, terminal limit 30 A → 30 A — too small
8 AWG: 50 A × 1.00 × 1.00 = 50 A, terminal limit 40 A → 40 A — passes
Voltage drop: 2 × 100 × 30 × 0.778 ÷ 1000 = 4.67 V (1.9%) — within the 3% guideline
Breaker: next standard size at or above 37.5 A = 40 A
Cost: 220 ft of 8 AWG copper (2 conductors × 100 ft × 1.10) × $0.95/ft = $209 + $15 breaker = $224 materials
For a 20 A continuous load, 120 V, 50 ft, copper 75 °C: required 25 A — 12 AWG is limited to 20 A by the 60 °C terminal rule, so the answer is 10 AWG, 2.48 V drop (2.1%), 25 A breaker, $83.50 materials. And a 50 A non-continuous load, 240 V, 150 ft, 40 °C ambient, 4–6 conductors: the derating (0.88 × 0.80 = 0.704) pushes the answer to 3 AWG — 4 AWG is 49.3 A after derating, just short of the 50 A required — 3.68 V drop (1.5%), 50 A breaker, $779 materials.
How much does wire cost? (US, 2026)
Prices are 2026 US ranges from US retail listings (THHN copper per foot, NM-B cable per foot, breakers each). Aluminium is roughly 45% cheaper per foot but needs a larger gauge. Check local prices before ordering.
| Wire / breaker | Typical price |
|---|---|
| 14 AWG THHN copper | $0.30–$0.40 per ft |
| 12 AWG THHN copper | $0.40–$0.50 per ft |
| 10 AWG THHN copper | $0.60–$0.70 per ft |
| 8 AWG THHN copper | $0.90–$1.00 per ft |
| 6 AWG THHN copper | $1.30–$1.40 per ft |
| 4 AWG THHN copper | $1.80–$2.00 per ft |
| 14/2 NM-B cable | $0.35–$0.50 per ft |
| 12/2 NM-B cable | $0.50–$0.70 per ft |
| 10/2 NM-B cable | $0.85–$1.10 per ft |
| 15–20 A single-pole breaker | $5–$10 each |
| 30–50 A double-pole breaker | $12–$25 each |
| 100 A main breaker | $80–$150 each |
Waste allowance
10% spare wire is the right default: terminations, the bends in the run and the few feet you lose at each box. Drop to 5% on a short straight run with the boxes already set, raise to 15% on a long run with several bends or a panel at the far end. The spare is priced in the cost line only — it never changes the gauge, because voltage drop and ampacity are calculated on the actual run length.
Frequently asked questions
What size wire do I need for 30 amps?
8 AWG copper for a 30 A continuous load at 240 V: the 125% rule makes it 37.5 A, and 10 AWG is limited to 30 A by the 60 °C terminal rule. For a 30 A non-continuous load, 10 AWG copper is enough (35 A at 75 °C, 30 A at the terminals).
What gauge wire for a 50 amp subpanel?
6 AWG copper at 75 °C for a 50 A non-continuous load at 30 °C with 1–3 conductors — 65 A derated, 55 A at the terminals. If the load is continuous, or the run is in a hot attic or a crowded conduit, the derating can push it to 4 AWG or 3 AWG.
How many amps can 12 gauge wire carry?
20 A at the terminals on a normal residential circuit — the 60 °C column of NEC Table 310.16 is 20 A, and that is what governs. The 75 °C column says 25 A, but that only applies if the breaker and the device are both marked 75 °C.
What size wire for 100 feet?
It depends on the load: a 20 A load at 120 V over 100 ft needs 10 AWG copper for ampacity, and the voltage drop is 4.96 V (4.1%) — over the 3% guideline — so the drop check pushes it to 8 AWG. Always check both ampacity and voltage drop on a long run.
Is aluminium wire safe?
Yes, when it is sized and installed correctly — aluminium needs one or two sizes larger than copper for the same amps, and the terminations must be rated CO/ALR or use approved connectors with anti-oxidant compound. Modern AA-8000 series aluminium is the code-approved alloy; the 1970s alloy that caused fires is no longer sold.