Home›Voltage Drop Calculator
Voltage Drop Calculator
A long wire run steals voltage: the same wire that is fine for a 20 ft run can starve a load 150 ft away. This calculator works out the voltage lost in volts and in percent, tells you whether it passes the NEC 3% guideline for a branch circuit, and finds the smallest wire size that brings it under 3%. It is an estimate for planning — always have a licensed electrician check the final sizing.
Calculate your voltage drop
Your results
How the voltage drop formula works
Voltage drop is Ohm’s law over the whole loop — the current times the resistance of the wire out and the wire back.
Single-phase: VD = 2 × L × I × R ÷ 1000 — L is the one-way length in feet, R is ohms per 1000 ft (NEC Chapter 9 Table 8)
Three-phase: VD = √3 × L × I × R ÷ 1000
Percent: VD% = VD ÷ circuit voltage × 100
Guideline: VD% ≤ 3% on a branch circuit (NEC 210.19(A)(1) FPN), 5% for feeder plus branch combined
Resistance is the NEC Chapter 9 Table 8 value at 75 °C — the same table every dedicated voltage drop calculator uses: 12 AWG copper 1.98 Ω/1000 ft, 10 AWG 1.24, 8 AWG 0.778, 6 AWG 0.491. The factor of 2 in the single-phase formula is the part people forget: the current travels out on one conductor and back on the other, so the run length counts twice. The worked example below verifies against a published example (150 ft, 20 A, 12 AWG copper at 120 V → 11.88 V, 9.9%).
Worked example
A 20 A load, 120 V, single-phase, 150 ft run on 12 AWG copper:
VD = 2 × 150 × 20 × 1.98 ÷ 1000 = 11.88 V
VD% = 11.88 ÷ 120 × 100 = 9.9% — FAIL (over the 3% guideline)
8 AWG: 2 × 150 × 20 × 0.778 ÷ 1000 = 4.67 V (3.9%) — still over
6 AWG: 2 × 150 × 20 × 0.491 ÷ 1000 = 2.95 V (2.5%) — PASS
Power lost as heat: 20 × 11.88 = 237.6 W
Cost to fix: 2 conductors × 150 ft of 6 AWG copper at $1.35/ft = $405 wire
For a 30 A load, 240 V, 100 ft on 10 AWG copper: VD = 2 × 100 × 30 × 1.24 ÷ 1000 = 7.44 V (3.1%) — just over, so 8 AWG (4.67 V, 1.9%) is the fix, $190 wire, 223.2 W lost on the 10 AWG. And a 40 A, 208 V three-phase, 200 ft run on 8 AWG copper: VD = 1.732 × 200 × 40 × 0.778 ÷ 1000 = 10.78 V (5.2%) — FAIL; 6 AWG is still 3.3%, so 4 AWG (4.27 V, 2.1%) is the answer, 431.2 W lost on the 8 AWG.
How much does wire cost? (US, 2026)
Prices are 2026 US ranges from US retail listings (THHN copper per foot). The cost line prices the recommended gauge only — upsizing one size roughly doubles the wire cost, which is why the shortest run is usually the cheapest fix. Check local prices before ordering.
| Wire | Typical price |
|---|---|
| 12 AWG THHN copper | $0.40–$0.50 per ft |
| 10 AWG THHN copper | $0.60–$0.70 per ft |
| 8 AWG THHN copper | $0.90–$1.00 per ft |
| 6 AWG THHN copper | $1.30–$1.40 per ft |
| 4 AWG THHN copper | $1.80–$2.00 per ft |
| 2 AWG THHN copper | $2.70–$2.90 per ft |
| Aluminium wire (same gauge) | About 45% less than copper |
| NM-B cable (12/2, 10/2) | $0.50–$1.10 per ft |
Waste allowance
There is no waste percentage on a voltage drop calculation — drop depends on the actual run length, not on how much spare wire you buy. If you are costing the job, add 10% to the wire length for terminations and bends: on the worked example that is 330 ft of 6 AWG instead of 300 ft, about $40 more. The cost line shows the exact run length; add the allowance when you order.
Frequently asked questions
What is an acceptable voltage drop?
3% on a branch circuit and 5% for the feeder plus the branch circuit together — the NEC Fine Print Note in 210.19(A)(1). It is a recommendation, not a hard rule, but most inspectors and electricians treat 3% as the design target because motors run hot and dim lights flicker below it.
How do you calculate voltage drop?
Multiply the current by the resistance of the wire out and back: VD = 2 × length × current × resistance per 1000 ft ÷ 1000 for single-phase, or √3 × length × current × resistance ÷ 1000 for three-phase. Resistance comes from NEC Chapter 9 Table 8 — 12 AWG copper is 1.98 Ω per 1000 ft.
What size wire for 100 feet at 20 amps?
At 120 V, 10 AWG copper drops 4.96 V (4.1%) over 100 ft — over the guideline — so you need 8 AWG (3.11 V, 2.6%). At 240 V the same run on 10 AWG drops only 2.1%, so 10 AWG passes. Higher voltage is the cheapest cure for a long run.
Does voltage drop matter for LED lights?
Yes — LEDs are more sensitive than old incandescent bulbs. Below about 108 V on a 120 V circuit (a 10% drop) many LED drivers dim, flicker or fail early. The 3% guideline keeps the voltage at 116 V or above, where LEDs behave normally.
How do you fix voltage drop?
Four options, cheapest first: shorten the run, raise the circuit voltage (120 V to 240 V halves the percentage), use a larger wire, or split the load across two circuits. On a new build, putting the subpanel near the load is usually cheaper than buying heavier wire.