How many watts is 15 amps? It depends on the voltage — 1,800 W at 120 V, 3,600 W at 240 V. This calculator converts amps to watts, watts to amps, or volt-amps, at any voltage, single-phase, three-phase or DC, with the power factor for motors and power supplies. It also shows the matching breaker size and what the load costs to run. It is an estimate for planning — always have a licensed electrician check the final sizing.
Convert amps and watts
Power factor is 1.0 for a heater or an incandescent bulb, and 0.8–0.95 for a motor, a compressor or a power supply. If you do not know it, use 1.0 for a resistive load and 0.9 for a motor. The breaker size assumes a continuous load (125% rule, NEC 210.19).
Your results
How the amps to watts formula works
It is Ohm’s law with the power factor added for AC loads.
Single-phase / DC: W = V × A × PF and A = W ÷ (V × PF)
Three-phase: W = √3 × V × A × PF and A = W ÷ (√3 × V × PF)
Volt-amps: VA = V × A (single-phase) or VA = √3 × V × A (three-phase) — watts = VA × power factor
Breaker: next standard size at or above amps × 1.25 for a continuous load — NEC 210.19
Running cost: cost per hour = kW × rate ($/kWh)
This is the method every dedicated amps-to-watts calculator uses (CalculatorHubZone, VIOX, EcoFlow, HVACBase): the same 15 A at 120 V is 1,800 W, and the same 10 A at 208 V three-phase with a 0.9 power factor is 3,242 W. The power factor is the only judgement call — 1.0 for a heater, 0.9 for a motor, 0.8 for an older fluorescent or an uncorrected power supply.
Worked example
15 A at 120 V, single-phase, power factor 1.0, rate $0.17/kWh:
W = 120 × 15 × 1.0 = 1,800 W (1.8 kW, 1,800 VA)
Breaker: 15 × 1.25 = 18.75 A → next standard size = 20 A
Running cost: 1.8 × $0.17 = $0.31 per hour, $7.34 per day, $220.32 per month
Maximum continuous load on that 20 A circuit: 20 × 0.8 = 16 A = 1,920 W
For 10 A at 208 V, three-phase, power factor 0.9: W = 1.732 × 208 × 10 × 0.9 = 3,242 W (3.24 kW, 3,603 VA), breaker 15 A, $0.55 per hour. And in reverse, 1,500 W at 120 V, power factor 1.0: A = 1,500 ÷ 120 = 12.5 A, breaker 20 A (12.5 × 1.25 = 15.63 A), $0.26 per hour.
What does an appliance cost to run? (US, 2026)
Watts are the nameplate rating; the monthly cost is at the typical daily use and the US average rate of $0.17/kWh (US average 18.19 cents/kWh, January–August 2026). Your rate is on your bill — California is about $0.34/kWh and Washington about $0.11/kWh. Check your own rate before ordering.
| Appliance | Watts | Typical use | Cost per month |
|---|---|---|---|
| LED bulb | 10 W | 5 h/day | $0.26 |
| Laptop | 50 W | 8 h/day | $2.04 |
| Refrigerator (average) | 150 W | 24 h/day, 50% duty | $9.18 |
| Microwave | 1,000 W | 0.5 h/day | $2.55 |
| Room air conditioner | 1,500 W | 6 h/day | $45.90 |
| Space heater | 1,500 W | 8 h/day | $61.20 |
| Electric water heater | 4,500 W | 2 h/day | $45.90 |
| EV charger | 7,200 W | 3 h/day | $110.16 |
| Central air conditioner | 3,500 W | 8 h/day | $142.80 |
Waste allowance
There is no waste percentage on a conversion — watts, amps and volts are exact numbers, not quantities you buy. The number to watch instead is the 80% rule: a breaker only carries 80% of its rating as a continuous load, so a 20 A circuit is good for 16 A (1,920 W at 120 V) and a 15 A circuit for 12 A (1,440 W). If your load is close to that limit, size the circuit up — a 15 A circuit running a 1,500 W heater is overloaded.
Frequently asked questions
How many watts is 15 amps?
1,800 W at 120 V (15 × 120), 3,600 W at 240 V, and 3,120 W at 208 V single-phase. On a 20 A circuit the most you can run continuously is 16 A — 1,920 W at 120 V — because of the 80% rule.
How many amps is 1000 watts?
8.33 A at 120 V (1,000 ÷ 120), 4.17 A at 240 V, and 4.81 A at 208 V. Divide the watts by the voltage; for a three-phase load divide by √3 × voltage as well, and by the power factor for a motor.
What is the difference between watts and volt-amps?
Watts is the real power that does work; volt-amps is the apparent power — volts times amps — that the wire and the breaker actually see. They are equal when the power factor is 1.0 (a heater); for a motor with a 0.9 power factor, 1,000 VA is only 900 W.
How many watts can a 20 amp breaker handle?
2,400 W at 120 V in theory, but only 1,920 W as a continuous load — the 80% rule (NEC 210.19). At 240 V the same breaker handles 4,800 W in theory and 3,840 W continuous.
What is power factor?
The fraction of the apparent power that does real work. A heater has a power factor of 1.0 — all of it works. A motor has 0.8–0.95 — the rest is magnetising current that heats the wire but does no work. A low power factor means more amps for the same watts, so bigger wires and breakers.