Home›Conduit Fill Calculator
Conduit Fill Calculator
How many wires fit in a conduit — and what is the smallest trade size that passes? This calculator uses the NEC Chapter 9 tables: the internal area of EMT, RMC and PVC conduit, the cross-section of each wire, and the fill limits of 53% for one wire, 31% for two wires and 40% for three or more. It is an estimate for planning — always have a licensed electrician check the final sizing.
Calculate your conduit fill
The ground wire counts too — every conductor in the conduit counts toward the fill, including the equipment grounding conductor. The wire areas are for THHN/THWN-2 (NEC Chapter 9 Table 5); other insulations (XHHW, NM-B) are fatter and fill faster.
Your results
How the conduit fill formula works
Fill is the total cross-section of the wires divided by the internal cross-section of the conduit.
Wire area: count × area per wire — NEC Chapter 9 Table 5 (THHN: 14 AWG 0.0097 in², 12 AWG 0.0133 in², 10 AWG 0.0211 in²)
Fill: total wire area ÷ conduit internal area × 100 — conduit internal area from NEC Chapter 9 Table 4
Limit: 53% for 1 wire, 31% for 2 wires, 40% for 3 or more wires — NEC Chapter 9 Table 1; 60% for a nipple 24 in or shorter — Note 4
Max wires: floor(conduit area × limit ÷ wire area), rounded up at 0.8 or more per Note 7
This uses the standard method, verified against published examples: 9 × 12 AWG THHN in 3/4 in EMT is 0.1197 in² against 0.533 in² internal — 22.5% fill against a 40% limit, and the smallest size that passes is 1/2 in EMT (0.304 × 0.40 = 0.1216 in², just enough). The judgement call is the wire type: the areas here are for THHN/THWN-2. XHHW-2 is fatter (12 AWG is 0.0181 in²) and NM-B cable is much fatter, so both fill faster.
Worked example
9 × 12 AWG THHN in 3/4 in EMT, not a nipple, 100 ft run:
Wire area: 9 × 0.0133 = 0.1197 in²
Conduit internal area (3/4 in EMT): 0.533 in²
Fill: 0.1197 ÷ 0.533 × 100 = 22.5% — PASS (limit 40% for 3+ wires)
Smallest size that passes: 1/2 in EMT, 0.304 × 0.40 = 0.1216 in² ≥ 0.1197 in² → 1/2 in
Max 12 AWG in 3/4 in EMT: 0.533 × 0.40 ÷ 0.0133 = 16.03 → 16 wires
Cost: 10 sticks of 3/4 in EMT at $11 + $10 fittings = $120
For 4 × 10 AWG + 1 × 12 AWG ground in 1/2 in EMT: 4 × 0.0211 + 0.0133 = 0.0977 in² ÷ 0.304 = 32.1% — PASS, smallest 1/2 in, max 10 AWG in 1/2 in is 5 wires, $85 conduit. And 20 × 12 AWG in 1 in EMT: 20 × 0.0133 = 0.266 in² ÷ 0.864 = 30.8% — PASS, but the same 20 wires in 3/4 in EMT are 49.9% — FAIL — so 1 in is the smallest size, $165 conduit.
How much does conduit cost? (US, 2026)
Prices are 2026 US ranges per 10 ft stick from US retail listings. RMC costs roughly twice EMT and is used where the conduit is exposed to damage; PVC is the cheapest and is used underground and outdoors. Check local prices before ordering.
| Conduit (10 ft stick) | EMT | RMC | PVC Sch 40 |
|---|---|---|---|
| 1/2 in | $6–$9 | $15–$20 | $4–$6 |
| 3/4 in | $9–$13 | $20–$28 | $6–$9 |
| 1 in | $13–$18 | $28–$38 | $8–$12 |
| 1-1/2 in | $23–$31 | $48–$62 | $15–$19 |
| 2 in | $32–$44 | $65–$85 | $20–$28 |
| Couplings & connectors | $1–$3 each | $2–$5 each | $1–$2 each |
Waste allowance
There is no waste percentage on a conduit fill calculation — fill depends on the wires, not on how much conduit you buy. If you are costing the job, add one extra 10 ft stick for the cuts and the fittings: on the worked example that is 11 sticks of 3/4 in EMT instead of 10, about $11 more. The cost line shows the exact run length in 10 ft sticks; add one stick when you order.
Frequently asked questions
How many wires can I put in a 3/4 inch conduit?
16 × 12 AWG THHN in 3/4 in EMT (0.533 in² × 40% ÷ 0.0133 in²). For 10 AWG it is 10 wires, for 14 AWG it is 22. The limit is 40% fill for three or more wires — NEC Chapter 9 Table 1.
What is the maximum conduit fill percentage?
40% for three or more wires, 31% for two wires and 53% for a single wire — NEC Chapter 9 Table 1. A short nipple 24 in or shorter is allowed 60%. The limits exist so the wires do not overheat and the pull does not damage the insulation.
Does the ground wire count for conduit fill?
Yes — every conductor in the conduit counts, including the equipment grounding conductor. A bare ground counts at its own area from NEC Chapter 9 Table 5; an insulated ground counts at the same area as the same size insulated wire.
Can I mix wire sizes in one conduit?
Yes — add up the area of each wire and compare the total against the fill limit. That is exactly what this calculator does with its three wire groups. The only restriction is that all conductors in one conduit must be insulated for the highest voltage present.
What size conduit for 3/4 inch EMT vs PVC?
The internal area is almost the same — 3/4 in EMT is 0.533 in², PVC Schedule 40 is 0.532 in² — so the fill is the same. PVC Schedule 80 is thicker-walled (0.507 in²) and holds slightly fewer wires. Choose by the location: PVC outdoors and underground, EMT indoors.