200+ free tools. No sign-up. No hidden fees.Explore the toolkit ↗
Find a tool ↗

Home›Breaker Size Calculator

Breaker Size Calculator

A breaker protects the wire, not the appliance — so the right size is the one just above the load, with the 125% rule applied to anything that runs for 3 hours or more. This calculator takes your load in watts or amps, applies the continuous-load rule, and gives you the standard breaker size from NEC 240.6(A) with the smallest wire that carries it. It is an estimate for planning — always have a licensed electrician check the final sizing.

Calculate your breaker size

⚠︎ Safety first — estimate only. Electrical work must comply with your local code (NEC in the US, BS 7671 in the UK, IEC elsewhere). Consult a licensed electrician before you buy or install anything. A wrong wire size is a fire risk — never treat a calculator result as code compliance.
Units:

The 125% rule: a continuous load must be sized as if it drew 25% more current (NEC 210.19(A)(1)). The wire must be at least as big as the breaker (NEC 240.4), and the 60 °C terminal limit applies on circuits up to 100 A — which is why a 20 A continuous load needs 10 AWG, not 12 AWG.

Your results

–
breaker size
–
load current
–
required ampacity
–
minimum wire

How the breaker size formula works

Breaker sizing is two steps: find the load current, then find the standard size above it.

Load current: I = P ÷ V (single-phase) or I = P ÷ (√3 × V) (three-phase)

Continuous load: required = I × 1.25 — NEC 210.19(A)(1)

Breaker: next standard size at or above the required ampacity — NEC 240.6(A): 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250 A

Wire: smallest gauge whose allowed ampacity ≥ breaker size — NEC 240.4, with the 60 °C terminal limit (NEC 110.14(C)) and the small-conductor caps: 14 AWG 15 A, 12 AWG 20 A, 10 AWG 30 A (NEC 240.4(D))

This uses the standard method, verified against published examples: a 4,500 W water heater at 240 V is 18.75 A, times 1.25 is 23.44 A, so a 25 A breaker with 10 AWG copper — because 12 AWG is capped at 20 A by the terminal rule. The judgement call is the continuous-load question: a water heater, an EV charger and a space heater run for 3 hours or more, so the 125% rule applies; a table saw or a microwave does not.

Worked example

A 4,500 W water heater, 240 V, single-phase, continuous load, 50 ft wire run, copper, 75 °C, 10% spare wire:

Load current: 4,500 ÷ 240 = 18.75 A

Required: 18.75 × 1.25 = 23.44 A (continuous)

Breaker: next standard size at or above 23.44 A = 25 A

Wire: 12 AWG is capped at 20 A by the 60 °C terminal rule, so 10 AWG copper

Cost: 110 ft of 10 AWG copper (2 conductors × 50 ft × 1.10) × $0.65/ft = $71.50 + $12 breaker = $83.50 materials

For a 1,500 W microwave, 120 V, continuous load, 50 ft: 1,500 ÷ 120 = 12.5 A × 1.25 = 15.63 A → 20 A breaker, 12 AWG copper, $57.50 materials. And an EV charger, 7,200 W, 240 V, continuous, 50 ft: 7,200 ÷ 240 = 30 A × 1.25 = 37.5 A → 40 A breaker, 8 AWG copper, $119.50 materials — this is the most common EV charger circuit in the US.

How much does a breaker and wire cost? (US, 2026)

Prices are 2026 US ranges from US retail listings (breakers each, NM-B cable per foot). A new circuit also needs a permit ($100–$400) and usually 1–2 hours of an electrician’s time ($150–$400). Check local prices before ordering.

Breaker / wireTypical price
15–20 A single-pole breaker$5–$10 each
25–30 A double-pole breaker$10–$15 each
40–50 A double-pole breaker$15–$25 each
60–100 A breaker$25–$90 each
GFCI breaker (15–20 A)$40–$60 each
AFCI breaker (15–20 A)$35–$55 each
12/2 NM-B cable$0.50–$0.70 per ft
10/2 NM-B cable$0.85–$1.10 per ft
8/3 NM-B cable$1.50–$2.00 per ft

Waste allowance

10% spare wire is the right default: terminations, the bends in the run and the few feet you lose at each box. Drop to 5% on a short straight run with the boxes already set, raise to 15% on a long run with several bends. The spare is priced in the cost line only — it never changes the breaker or the gauge, because both are sized on the load, not on the wire length.

Frequently asked questions

What size breaker do I need for 4500 watts?

A 25 A double-pole breaker at 240 V: 4,500 ÷ 240 = 18.75 A, times 1.25 for a continuous load is 23.44 A, and the next standard size is 25 A. The wire is 10 AWG copper — 12 AWG is capped at 20 A by the 60 °C terminal rule.

What size breaker for a 30 amp load?

A 30 A breaker for a non-continuous 30 A load, or a 40 A breaker if it runs for 3 hours or more (30 × 1.25 = 37.5 A, next size up is 40 A). The wire is 10 AWG copper for the 30 A breaker and 8 AWG for the 40 A breaker.

Can I use a 20 amp breaker on 14 gauge wire?

No — 14 AWG copper is capped at 15 A by NEC 240.4(D), even though the 75 °C column says 20 A. A 20 A breaker needs 12 AWG copper as a minimum.

What size breaker for an EV charger?

A 7,200 W (30 A) charger needs a 40 A breaker and 8 AWG copper, because it is a continuous load: 30 × 1.25 = 37.5 A. An 11,500 W (48 A) charger needs a 60 A breaker and 6 AWG copper.

What happens if the breaker is too big?

The wire overheats before the breaker trips — the breaker is there to protect the wire, and an oversized breaker lets the wire carry more current than it can safely handle. That is a fire risk, and it is why the code sizes the breaker to the wire, not to the appliance.

Related calculators