A radiant floor is a grid of warm water pipes under the floor, and the design is three numbers at once: how much tubing, how many loops, and how hot the water must be. Too little tubing and the floor never gets warm; loops too long and the far end runs cold. Enter the zone, the spacing and the heat loss to get the tubing, the loops, the floor and supply temperatures, the flow and the cost — before the concrete is poured over it.
Calculate radiant floor heating
Your results
How the radiant floor formula works
Field tubing (ft) = area (sq ft) × 12 ÷ spacing (in) · Loops = ceil(field ÷ (max loop − 2 × leader)) · Total tubing = field + loops × 2 × leader · Floor surface temp = room temp + output per sq ft ÷ 1.9 · Supply water temp = surface temp + output × R-value + ΔT ÷ 2 · Flow (GPM) = heat loss ÷ (500 × ΔT)
Feet of tube per square foot is simply 12 divided by the spacing in inches: 12 in spacing is one foot of tube per square foot of floor, 6 in spacing is two feet, because at half the spacing you fit twice as many passes across the same area (gettheamount.com). Each tube size has its own maximum loop length — about 250 ft for 3/8 in PEX, 300 ft for 1/2 in, 400 ft for 5/8 in and 500 ft for 3/4 in — because a larger inside diameter lets a given flow travel farther before friction loss becomes too much for a typical circulator. The leader run to the manifold counts against that limit twice, once out and once back, so a distant manifold eats into the usable budget before any field tube is laid at all. The floor surface temperature is the real constraint: every degree the floor runs above the room delivers 1.9 BTU/hr per sq ft (Viega radiant heating design manual), and the recommended maximum surface is 85°F — a floor that needs more than 32.3 BTU/hr per sq ft cannot carry the load alone, whatever the water temperature. The supply temperature adds the drop through the floor covering (output × R-value) and half the loop temperature drop.
Worked example
Worked example: 400 sq ft zone, 12 in spacing, 12,000 BTU/hr
A 400 sq ft zone at 12 in spacing, losing 12,000 BTU/hr, 1/2 in PEX (300 ft max), 20 ft manifold leaders, 20°F drop, 68°F room, R-value 1.0 above the tubing, PEX at $0.60/ft, manifold $250, thermostat $150:
- Field tubing: 400 × 12 ÷ 12 = 400 ft
- Loops: usable per loop 300 − 2 × 20 = 260 ft; ceil(400 ÷ 260) = 2 loops of 240 ft
- Total tubing: 400 + 2 × 40 = 480 ft
- Output: 12,000 ÷ 400 = 30.0 BTU/hr/sq ft
- Floor surface: 68 + 30.0 ÷ 1.9 = 83.8°F — under the 85°F limit
- Supply water: 83.8 + 30.0 × 1.0 + 10 = 123.8°F
- Flow: 12,000 ÷ (500 × 20) = 1.2 GPM
- Cost: PEX 480 × $0.60 = $288 + manifold $250 + thermostat $150, total $688
Cross-check: 4calculators.com uses the same six formulas with the same maximum loop lengths and the same 85°F surface check. A second check from liczgrupa.pl (Viega manual): a room losing 4,000 BTU/hr through 180 sq ft needs 22.2 BTU/hr per sq ft, which puts a tiled surface at 79.7°F in a 68°F room — this calculator matches it. A third from best-calculators.com: a 2,000 sq ft system at 9 in spacing and 70,000 BTU/hr needs 2,933 ft of PEX and 12 loops by their flat-10% leader method; this calculator counts the actual manifold run instead and gives 3,107 ft and 11 loops for a 20 ft leader — the methods differ, and the actual-run count is the honest one when the manifold is far from the zone.
The floor surface temperature is the constraint that quietly kills more radiant designs than tubing length ever does — check it before the floor is covered, not after a room stays cold.
How much does radiant floor heating cost? (US, 2026)
Typical 2026 US material prices for one zone. A full installed system runs $6-$15 per sq ft including the boiler, controls and labour.
| Item | Typical cost (US, 2026) |
|---|---|
| PEX tubing, 1/2 in, per ft | $0.40-$0.80 |
| Manifold, 2-4 port | $150-$400 |
| Thermostat, radiant | $100-$200 |
| Circulator pump | $150-$300 |
| Installed system, per sq ft | $6-$15 |
| 400 sq ft zone, materials | ~$688 |
| US 2026 prices, checked November 2026. Sources: 4calculators.com radiant floor loop length calculator, liczgrupa.pl radiant floor heating calculator, best-calculators.com hydronic heating calculator. | |
Waste allowance
There is no waste percentage on radiant tubing — the field length is exact, and the leaders are counted explicitly. The allowance to plan for is one extra loop port on the manifold: buy a manifold with one more port than the loop count, so a future zone or a split loop has somewhere to go. PEX comes in coils (100, 300, 500 ft), so round the total up to the next coil size and keep the offcut — a 20 ft offcut is exactly what a repair needs.
Frequently asked questions
How much PEX tubing do I need for radiant floor heating?
Feet of tube per square foot is 12 divided by the spacing in inches: 12 in spacing is one foot per square foot, 6 in spacing is two feet. A 400 sq ft zone at 12 in spacing needs 400 ft in the field, plus the leaders back to the manifold — 480 ft total with 20 ft leaders and 2 loops.
How many loops does a radiant floor need?
Divide the field tubing by what is left of the maximum loop length after the leaders: loops = ceil(field / (max loop - 2 x leader)). A 1/2 in PEX loop tops out around 300 ft, so a 400 ft field with 20 ft leaders needs 2 loops. A fraction of a loop over what whole loops can carry needs one more loop, not a single loop stretched past its limit.
How hot should radiant floor water be?
Supply water is usually 100-140 F, far cooler than radiators. It follows from the floor surface temperature plus the drop through the floor covering plus half the loop drop: a 400 sq ft zone at 30 BTU/hr/sq ft with R-1.0 covering needs about 124 F supply. Hardwood and carpet need hotter water than tile for the same output.
What is the maximum floor surface temperature?
85 F is the recommended maximum for all floors (Viega); CSA B214 allows 88 F in living space, 91 F in bathrooms and 95 F along outside walls. A floor that needs more than 32.3 BTU/hr per sq ft at 85 F cannot carry the load alone — tighten the spacing or add a second heat source.
What spacing should radiant floor tubing be?
12 in on centre is the usual slab default. Use 6-9 in in high-loss rooms and bathrooms, where the floor has to give more heat per square foot. Tighter spacing is not free extra output — halving the spacing roughly doubles both the tube used and, often, the loop count.