What size furnace does your house need — 40,000, 60,000, 80,000 or 100,000 BTU? This calculator works out the heating load from your floor area and climate zone, adds the standard 15% sizing margin, and divides by the furnace efficiency (AFUE) to give the input size to buy. The result is an estimate for planning — a licensed HVAC professional should confirm the final size with a Manual J calculation, and an oversized furnace short-cycles and wears out early.

Calculate your furnace size

⚠︎ Sizing is an estimate only. Sizing must be confirmed by a licensed HVAC professional and comply with your local code. Improper sizing wastes energy and can damage equipment — never treat a calculator result as a final equipment selection.
Units:

The zone factor is the heating load in BTU per hour per square foot at an 8 ft ceiling: 30 in the warmest zones rising to 60 in the coldest. Furnaces are sized at about 115% of the heating load (CalculateHVACLoad) — the margin covers the coldest night and the morning warm-up. The input size is the output divided by the AFUE: a 95% furnace turns 95 cents of every gas dollar into heat.

Your results

–
heating load
–
furnace output needed
–
furnace input needed
–
standard size to buy

How the furnace size formula works

A furnace is sized to the heating load of the house, plus a margin, divided by its efficiency.

Heating load: BTU/hr = floor area × zone factor × (ceiling ÷ 8) × insulation factor

Output needed: output = load × 1.15 — the standard 15% sizing margin

Input needed: input = output ÷ AFUE — AFUE is the fraction of the fuel that becomes heat

Standard size: the smallest standard furnace (40,000 / 60,000 / 80,000 / 100,000 / 120,000 BTU) at or above the input

The zone factor is the published 30–60 BTU per square foot range, by IECC climate zone: 30 in zone 1, 35 in zone 2, 40 in zone 3, 45 in zone 4, 50 in zone 5, 55 in zone 6, 60 in zone 7. The 15% margin is the CalculateHVACLoad rule ("furnaces are sized at ~115% of heating load"). The cross-check: HVACsCalculator gives a 60,000 BTU/hr input for a 1,500 sq ft zone-4 home at 95% AFUE — 1,500 × 40 = 60,000 BTU/hr, the same load with a zone factor of 40 and no margin. The one judgement call is the zone factor: a house with a lot of glass or a leaky envelope needs the top of its zone range.

Worked example

A 1,500 sq ft home, 8 ft ceilings, climate zone 4, average insulation, 95% AFUE furnace:

Heating load: 1,500 × 45 × 1.0 × 1.0 = 67,500 BTU/hr

Output needed: 67,500 × 1.15 = 77,625 BTU/hr

Input needed: 77,625 ÷ 0.95 = 81,711 BTU/hr

Standard size: 80,000 is short, so buy a 100,000 BTU furnace

Cost: installed $5,250 (mid-range) + about $1.23/hour at full fire on gas at $1.50/therm

For a 1,000 sq ft home, 8 ft ceilings, zone 2, good insulation, 95% AFUE: load = 1,000 × 35 × 0.8 = 28,000 BTU/hr, output 32,200, input 33,895 → a 40,000 BTU furnace, $3,250 installed. And a 2,500 sq ft home, 9 ft ceilings, zone 6, good insulation, 98% AFUE: load = 2,500 × 55 × 1.125 × 0.8 = 123,750 BTU/hr, output 142,313, input 145,217 — over 120,000 BTU/hr, so a single residential furnace will not cover it: two furnaces or a boiler system.

How much does a furnace cost? (US, 2026)

Prices are 2026 US mid-range installed prices from Angi / HomeAdvisor guides (equipment + installation + removal of the old unit). A high-efficiency condensing furnace also needs a condensate drain and PVC venting, which can add $500–$1,500. Gas is priced at $1.50/therm. Check local prices before ordering.

Furnace sizeInstalled (mid-range)Running cost at full fire
40,000 BTU$2,500–$4,000$0.60/hour
60,000 BTU$3,000–$4,500$0.90/hour
80,000 BTU$3,500–$5,500$1.20/hour
100,000 BTU$4,000–$6,500$1.50/hour
120,000 BTU$4,500–$7,500$1.80/hour

Waste allowance

There is no waste percentage on a furnace calculation — the load is exact once the house is measured. The margin that matters is the 15% sizing margin, which is already in the result. Do not add another margin on top: a furnace two sizes too big short-cycles, leaves cold spots and fails early.

Frequently asked questions

What size furnace do I need for 1500 sq ft?

About 67,500 BTU/hr of heating load in climate zone 4 with average insulation — 77,625 BTU/hr of output with the 15% margin, 81,711 BTU/hr of input at 95% AFUE, so a 100,000 BTU furnace. In a warm zone 2 home the same house needs an 80,000 BTU furnace.

What size furnace do I need for 2000 sq ft?

About 90,000 BTU/hr of load in zone 4 (2,000 × 45), 103,500 BTU/hr of output, 108,947 BTU/hr of input at 95% AFUE — a 120,000 BTU furnace. In zone 5 the same house needs over 120,000 BTU/hr of input, so two furnaces or a boiler.

Is a bigger furnace better?

No — an oversized furnace heats the house so fast it switches off before the air has mixed, leaving cold spots, and the constant starting and stopping wears the heat exchanger out. Size to the load plus the 15% margin, never two sizes up.

What does 95% AFUE mean?

Annual Fuel Utilization Efficiency: 95% of the fuel becomes heat in the house and 5% goes up the flue. An 80% furnace wastes 20 cents of every gas dollar. A 95% condensing furnace costs more to buy but needs a smaller input size for the same output.

How much does a new furnace cost?

About $2,500–$4,000 installed for a 40,000 BTU furnace, $3,500–$5,500 for 80,000 BTU, and $4,000–$6,500 for 100,000 BTU (2026 US mid-range prices). A high-efficiency condensing furnace can add $500–$1,500 for the condensate drain and PVC venting.