Home›Heat Loss Calculator
Heat Loss Calculator
How much heat escapes through the walls, windows, roof and floor — plus the air that leaks in? This calculator adds up the loss through each surface (U-value × area × temperature difference) and the ventilation loss, so you can see exactly which part of the room is costing you heat. It is a steady-state estimate, not a Manual J calculation — a licensed HVAC professional should confirm the final equipment size.
Calculate your heat loss
The exterior wall length is the total length of walls that face outside — for a corner room, add the two outside walls together. The window area is the total glazing in those walls. One air change per hour is a typical older home; a tight new home is about 0.5, a draughty one 1.5 or more.
Your results
How the heat loss formula works
Heat escapes through every surface and with every breath of air that leaks out. The formula adds up each path separately, so you can see which one matters.
Each surface: Q = U × A × ΔT — U is the heat-loss coefficient (W/m²K), A is the area, ΔT is the inside–outside temperature difference
Ventilation: Q = 0.33 × ACH × volume (m³) × ΔT — 0.33 Wh/m³K is the heat capacity of air
Total: Q = walls + windows + roof + floor + ventilation (watts)
BTU/hr: BTU/hr = watts × 3.41214
This uses the standard method, with the same U-value presets: walls 2.1 / 1.0 / 0.3, windows 5.0 / 2.8 / 1.4, roof 2.3 / 0.7 / 0.16, floor 0.9 / 0.5 / 0.22 W/m²K for poor / average / good insulation. It matches a published worked example — a 4 × 3.5 m bedroom with 2 m² of double glazing at a 24 °C difference loses 402 W through the walls, 134 W through the windows and 277 W through ventilation, 813.6 W in total before the roof and floor are counted. The one judgement call is the air-change rate: 1.0 ACH is a typical older home, 0.5 a tight new one, 1.5 a draughty one.
Worked example
A 12 × 15 ft room, 8 ft ceiling, 27 ft of exterior wall, 20 sq ft of windows, average insulation, 70 °F inside, 20 °F outside (ΔT 50 °F = 27.8 °C), 1.0 ACH:
Wall area: 27 × 8 − 20 = 196 ft² (18.21 m²) → 1.0 × 18.21 × 27.8 = 506 W
Windows: 20 ft² (1.86 m²) → 2.8 × 1.86 × 27.8 = 145 W
Roof: 180 ft² (16.72 m²) → 0.7 × 16.72 × 27.8 = 325 W
Floor: 180 ft² → 0.5 × 16.72 × 27.8 = 232 W
Ventilation: 0.33 × 1.0 × 40.78 m³ × 27.8 = 374 W
Total: 1,582 W (5,396 BTU/hr) — with the 10% warm-up margin, 1,740 W (5,936 BTU/hr)
For the a2z.tools bedroom — 4 × 3.5 m, 2.5 m ceiling, 7.5 m of exterior wall, 2 m² of double glazing, 21 °C inside, −3 °C outside, 1.0 ACH: walls 402 W, windows 134 W, ventilation 277 W — 813.6 W before the roof and floor, exactly as a2z.tools publishes. Add the roof (235 W) and floor (168 W) and the full loss is 1,217 W (4,152 BTU/hr). And a poorly insulated 12 × 15 ft room at the same temperatures loses about 3,180 W (10,852 BTU/hr) — more than twice as much, which is why insulation pays for itself.
What does it cost to replace the heat — or fix the loss? (US, 2026)
Equipment prices are 2026 US ranges from US retail listings; insulation prices are Angi ranges. The heater price is the equipment to replace the loss; the fix price is the typical cost of cutting the biggest loss. Check local prices before ordering.
| Item | Typical price |
|---|---|
| Space heater, up to 10,000 BTU/hr | $40–$150 |
| Mini-split, 12,000–24,000 BTU/hr (installed) | $2,500–$6,000 |
| Gas furnace, 40,000–100,000 BTU/hr (installed) | $3,000–$6,500 |
| Attic insulation top-up (blown-in) | $1,500–$3,500 |
| Blown-in wall insulation | $2,000–$4,000 |
| Double-glazed window upgrade (per window) | $400–$1,000 |
| Air sealing (caulk + weatherstripping) | $500–$1,500 |
Waste allowance
There is no waste percentage on a heat loss calculation — the loss is exact once the surfaces and temperatures are known. The margin that matters is the 10% warm-up allowance on the heater size: a heater sized exactly to the steady-state loss takes too long to warm a cold room in the morning.
Frequently asked questions
How do you calculate heat loss of a room?
Add up the loss through each surface — U-value × area × temperature difference — plus the ventilation loss, 0.33 × air changes per hour × room volume × temperature difference. A 12 × 15 ft room with average insulation at 70 °F inside and 20 °F outside loses about 1,582 W (5,396 BTU/hr).
What is a good U-value for a wall?
About 0.3 W/m²K or lower for a well-insulated wall, about 1.0 for a standard insulated wall, and about 2.1 for an uninsulated solid wall. Windows are much worse: 1.4 for good low-e double glazing, 2.8 for standard double glazing, 5.0 for single glazing.
How many watts to heat a room?
It depends on the loss, not the size alone: a 12 × 15 ft room with average insulation needs about 1,582 W at a 50 °F temperature difference, and about 3,180 W with poor insulation. Size the heater to the loss plus a 10% warm-up margin.
What is ACH in heat loss?
Air changes per hour — how many times the room’s air is replaced by outside air in an hour. A tight new home is about 0.5 ACH, a typical older home about 1.0, a draughty one 1.5 or more. Each air change costs 0.33 × volume × temperature difference in watts.
Does insulation really cut heat loss?
Yes — more than anything else. The same 12 × 15 ft room loses 3,180 W with poor insulation and 1,582 W with average insulation, and under 800 W with good insulation. The walls are usually the biggest single loss, followed by the roof.