What size electrical box do I need? Every wire, device, clamp and ground inside a box takes up space, and NEC 314.16 counts each one in cubic inches. This calculator adds it all up — conductors at their full allowance, each device at twice the largest conductor, the clamps and the grounds at one allowance each — and tells you the smallest standard box that fits. It is an estimate for planning — always have a licensed electrician check the final sizing.

Calculate your box fill

⚠︎ Safety first — estimate only. Electrical work must comply with your local code (NEC in the US, BS 7671 in the UK, IEC elsewhere). Consult a licensed electrician before you buy or install anything. A wrong wire size is a fire risk — never treat a calculator result as code compliance.
Units:

Count every conductor that enters the box, including the ones that just pass through — a wire that loops in and out counts twice. A pigtail that stays in the box does not count. The allowances are from NEC Table 314.16(B).

Your results

–
volume required
–
verdict
–
spare space
–
smallest box that fits

How the box fill formula works

Box fill is an allowance in cubic inches for everything inside the box.

Allowances: 14 AWG 2.0 in³, 12 AWG 2.25 in³, 10 AWG 2.5 in³, 8 AWG 3.0 in³, 6 AWG 5.0 in³ — NEC Table 314.16(B)

Conductors: each conductor × its allowance — a wire that passes through counts twice

Devices: each yoke × 2 × allowance of the largest conductor on it — NEC 314.16(B)(4)

Clamps: all internal clamps together × 1 allowance of the largest conductor — NEC 314.16(B)(2)

Grounds: all grounds together × 1 allowance for up to 4, plus 1/4 allowance for each extra ground — NEC 314.16(B)(5)

Fittings: all internal fittings together × 1 allowance — NEC 314.16(B)(3)

This uses the standard method, verified against published examples: 4 × 14 AWG conductors + 1 device + clamps + 2 grounds is 8 + 4 + 2 + 2 = 16 in³, which fits an 18 in³ single-gang box with 2 in³ spare. The judgement call is the conductor count: every conductor that enters the box counts, including the ones that just pass through — a wire that loops in and out counts twice — but a pigtail that stays inside the box does not count.

Worked example

A box with 4 × 14 AWG conductors, 1 device (receptacle), internal clamps, 2 grounds, single-gang 18 in³ box:

Conductors: 4 × 2.0 = 8 in³

Device: 1 × 2 × 2.0 = 4 in³

Clamps: 1 × 2.0 = 2 in³

Grounds: 1 × 2.0 = 2 in³

Total: 8 + 4 + 2 + 2 = 16 in³ — fits an 18 in³ box, PASS, 2 in³ spare, room for 1 more 14 AWG conductor

Cost: $2 box + $6 device + $2 cover = $10 materials

For the LaborSam example — 6 × 12 AWG + 3 × 10 AWG conductors, 2 devices, clamps, 3 grounds (largest 10 AWG): conductors 6 × 2.25 + 3 × 2.5 = 21 in³, devices 2 × 2 × 2.25 = 9 in³, clamps 2.5 in³, grounds 2.5 in³ — total 35.0 in³, so the smallest box is the 4-11/16 in square × 2-1/8 in (42 in³), $23 materials. And 8 × 12 AWG, no devices, clamps, 4 grounds in a 21 in³ box: 18 + 2.25 + 2.25 = 22.5 in³ — FAIL, smallest box is the 4-11/16 in square × 1-1/2 in (25.5 in³).

How much does a box cost? (US, 2026)

Prices are 2026 US ranges from US retail listings (boxes, devices and covers each). A remodel (old-work) box costs a little more than a new-work box. Check local prices before ordering.

Box / deviceTypical price
Single-gang plastic box, 18 in³$1–$3
4 in square metal box, 21 in³$3–$6
4 in square metal box, 30.3 in³$4–$7
4-11/16 in square box, 42 in³$7–$11
4 in octagonal box, 21.5 in³$3–$5
Duplex receptacle$2–$6 each
Single-pole switch$2–$5 each
GFCI receptacle$15–$25 each
Blank cover plate$1–$3 each

Waste allowance

There is no waste percentage on a box fill calculation — the volume is fixed by the wires and devices you put in the box. The number that matters for the budget is the box size: going one size up usually costs $2–$4 more and saves an hour of fighting a crowded box. If the calculator says FAIL, buy the next size up — a box that is too small will fail inspection.

Frequently asked questions

What size electrical box do I need?

Add up the volume: each conductor takes its allowance (14 AWG 2.0 in³, 12 AWG 2.25 in³, 10 AWG 2.5 in³), each device takes twice the largest conductor, and the clamps and grounds take one allowance each. A single receptacle with 4 × 14 AWG wires needs 16 in³ — an 18 in³ single-gang box.

How many wires can go in a single gang box?

An 18 in³ single-gang box holds 9 × 14 AWG conductors with no device, or 4 × 14 AWG conductors plus one device, clamps and grounds. For 12 AWG it is 8 conductors with no device, or 3 conductors plus a device. The device is what eats the space.

Do ground wires count for box fill?

Yes — all the grounds together count as one conductor allowance (for up to 4 grounds), plus a quarter allowance for each ground beyond 4. Two grounds in a box count the same as one.

What is the volume of a 4 inch square box?

A 4 in square × 1-1/2 in box is 21 in³, and a 4 in square × 2-1/8 in box is 30.3 in³ (NEC Table 314.16(A)). The deeper 4-11/16 in square × 2-1/8 in box is 42 in³ — the biggest common box.

Can I use a bigger box than required?

Yes — the code sets a minimum, not a maximum. A bigger box is easier to work in, runs cooler and passes inspection more easily. The only cost is a few dollars and a deeper wall cavity.