HVAC Duct Size Calculator
A duct that is too small whistles, starves the room and wears out the blower; a duct that is too big costs more and moves air so slowly it never mixes. The size follows the airflow and the friction rate, not a guess. Enter the CFM and the friction rate to get the exact diameter, the stock size to buy, the rectangular equivalent and the velocity check, before you order sheet metal you cannot return.
Calculate duct size
Your results
How the duct size formula works
D = (0.0992 × CFM1.9 ÷ friction rate)1/5.02 · Velocity (fpm) = CFM ÷ duct area (sq ft) · Rectangular equivalent diameter De = 1.30 × (a × b)0.625 ÷ (a + b)0.25
The diameter comes from the ACCA Manual D equal-friction formula (thehomehacksdiy.com): the duct is sized so the pressure drop per 100 ft equals the friction rate you choose. The standard residential rate is 0.08 in. w.c. per 100 ft; 0.10 for short runs, 0.05 for long or quiet runs. Because duct is sold in fixed steps — 6, 7, 8, 9, 10 inches and up — the exact diameter is always rounded up to the next stock size, and the velocity is re-checked in the size you will actually buy (gettheamount.com). Rectangular duct is matched by the ASHRAE equivalent diameter (thermist.com), not by equal area: a 16 × 10 in rectangular duct has the same friction as a 13.7 in round duct. Flex duct is upsized one size because its internal friction runs about 50% higher than rigid metal. Return ducts should run about 20-25% larger than supply for the same airflow to stay quiet.
Worked example
Worked example: 1,000 CFM at 0.08 in. w.c. per 100 ft
A 1,000 CFM supply trunk in rigid metal at the standard 0.08 friction rate, 10 in rectangular height, 25 ft of duct at $8/ft, 4 fittings at $25 each:
- Exact diameter: (0.0992 × 1,0001.9 ÷ 0.08)1/5.02 = 14.26 in
- Stock size: 15 in round; velocity 1,000 ÷ 1.227 sq ft = 815 fpm — within the 900 fpm residential guideline
- Rectangular equivalent: 18 × 10 in (equivalent diameter 14.51 in); velocity 1,000 ÷ 1.25 sq ft = 800 fpm
- Cost: duct 25 × $8 = $200 + fittings 4 × $25 = $100, total $300
Cross-check: thermist.com gives 14.3 in at 900 fpm (exact diameter) for 1,000 CFM at 0.08, and 13.7 in at 983 fpm at 0.10 — this calculator gives 14.26 in and 13.64 in for the same two cases. A second check from thehomehacksdiy.com: a 3-ton system at 1,200 CFM and 0.08 needs a 16 in round trunk at 859 fpm — this calculator gives 15.28 in exact, 16 in stock, 859 fpm. A third from pockethvac.com: 700 CFM at 0.10 takes a 12 in duct — this calculator gives 11.92 in exact, 12 in stock.
Verify a rectangular size with a full ductulator before final install — the equivalent-diameter method is an approximation, and a tight aspect ratio (over about 4:1) costs more friction than the formula shows.
How much does ductwork cost? (US, 2026)
Typical 2026 US prices for rigid galvanized duct, installed. Flex duct runs cheaper per foot but is upsized one size.
| Item | Typical cost (US, 2026) |
|---|---|
| Rigid round duct, per lin ft (installed) | $6-$15 |
| Flex duct, per lin ft (installed) | $3-$6 |
| Rectangular duct, per lin ft (installed) | $8-$18 |
| Elbow / take-off / register boot, each | $15-$40 |
| Full duct system, average home | $2,000-$5,000 |
| 1,000 CFM trunk, 25 ft + 4 fittings | ~$300 |
| US 2026 prices, checked November 2026. Sources: thermist.com duct sizer, pockethvac.com ductulator, thehomehacksdiy.com HVAC duct sizing calculator. | |
Waste allowance
There is no waste percentage on a duct size — the diameter is exact once the airflow and friction rate are known. The allowance to plan for is fittings: every elbow, take-off and register boot adds friction that the straight-duct math does not count. Count the fittings in the run and add them to the cost; if the run has more than about four fittings, drop the friction rate one step (0.08 to 0.05) and size the duct again.
Frequently asked questions
What size duct do I need for 1,200 CFM?
A 3-ton system moves about 1,200 CFM (400 CFM per ton). At the standard 0.08 in. w.c. per 100 ft friction rate that needs a 16 in round trunk duct, running at about 859 fpm — right under the 900 fpm residential supply limit. Branch ducts to individual rooms are sized smaller, based on each room's own CFM share.
What is a good friction rate for residential duct?
0.08 in. w.c. per 100 ft is the standard residential design rate under ACCA Manual D. Use 0.10 for short runs and 0.05 for long runs or where quiet matters. The project specification or Manual D sets the real target.
How do I convert a round duct to rectangular?
Use the ASHRAE equivalent diameter, not equal area: De = 1.30 x (a x b)^0.625 / (a + b)^0.25. A 16 x 10 in rectangular duct equals a 13.7 in round duct. Equal area would give 15 x 10 in, which is slightly undersized.
Why is my duct noisy?
Velocity is usually the cause. Residential supply duct should stay under about 900 fpm and returns under about 700 fpm. A 14 in duct carrying 1,000 CFM runs at about 935 fpm — one size up to 16 in drops it to about 717 fpm and the whistle goes away.
Is flex duct sized the same as rigid metal?
No — flex duct is upsized one size, because its internal friction runs about 50% higher than rigid metal and it sags between supports. A run that needs a 14 in rigid duct takes a 15 in flex duct, and the run should be pulled tight with no sag.