Home›Attic Ventilation Calculator
Attic Ventilation Calculator
Work out the attic ventilation for a house — the net free area (NFA) the code requires, the split between intake and exhaust, and how many feet of ridge vent, soffit vent or box vents that is.
Calculate your attic ventilation
The code (IRC R806.2) requires net free ventilating area of at least 1/150 of the attic floor area, reduced to 1/300 when a vapour barrier is present (Class I or II) or when 40–50% of the ventilation is at least 3 ft above the eave vents. The area is split evenly between intake (soffit) and exhaust (ridge or box). The NFA is the open area through the vent — a vent’s louvres and screens cut the gross area by 25–50%, so always use the manufacturer’s NFA rating.
Your results
How attic ventilation is calculated (IRC R806.2)
The code is simple: a minimum amount of open area, split evenly between low intake and high exhaust. The area is the net free area (NFA) — the actual open area through the vent, not the size of the hole.
Total NFA: attic floor area ÷ 150 (or ÷ 300 with a vapour barrier)
Exhaust NFA: total NFA ÷ 2
Intake NFA: total NFA ÷ 2
Ridge vent: exhaust NFA ÷ 18 sq in per ft
Box vent: exhaust NFA ÷ 50 sq in each
Continuous soffit vent: intake NFA ÷ 9 sq in per ft
Individual soffit vent: intake NFA ÷ 50 sq in each
These are the IRC R806.2 rule and the manufacturer NFA ratings used by the HomeYardStick and CalcFormula attic-ventilation calculators: ridge vent 18 sq in per lin ft, box vent 50 sq in, gable vent 80 sq in, turbine 120 sq in, continuous soffit vent 9 sq in per lin ft, individual soffit vent 50 sq in. The worked example below is the CalcFormula example: a 2,000 sq ft attic at 1/300 needs 960 sq in, 26.7 ft of ridge vent and 53.3 ft of soffit vent.
Worked example
An attic 2,000 sq ft with a vapour barrier (1/300), ridge vent exhaust and continuous soffit intake:
Total NFA: 2,000 ÷ 300 × 144 = 960 sq in
Exhaust: 960 ÷ 2 = 480 sq in
Intake: 960 ÷ 2 = 480 sq in
Ridge vent: 480 ÷ 18 = 26.7 ft
Soffit vent: 480 ÷ 9 = 53.3 ft
A 40 × 30 ft attic (1,200 sq ft) at 1/300 needs 576 sq in total: 16 ft of ridge vent (4 × 4 ft sections) and 32 ft of continuous soffit (4 × 8 ft strips), costing about $112. The same attic at 1/150 needs 1,152 sq in: 32 ft of ridge vent and 64 ft of soffit. With box vents instead of ridge, the 1,200 sq ft attic needs ceil(288 ÷ 50) = 6 box vents, costing about $132.
How much does attic ventilation cost? (US, 2026)
Prices are 2026 US retail ranges (Home Depot / Lowe’s lists). Ventilation is one of the cheapest things you can add to a roof — the cost of the vents is small, and the cost of not having them is a hot attic, a short shingle life and moisture damage. Check local prices before ordering.
| Item | Typical price |
|---|---|
| Ridge vent, 4 ft section | $4–$6 per lin ft |
| Box (turtle) vent | $15–$30 each |
| Gable vent | $40–$80 each |
| Turbine (whirlybird) vent | $50–$100 each |
| Continuous soffit vent | $1–$2 per lin ft |
| Individual soffit vent | $5–$10 each |
| Ridge cap shingles (to cover ridge vent) | $40–$60 per bundle |
Waste allowance
Ventilation has no waste allowance — it is a code minimum, not an order quantity. Round each vent count UP to whole vents: a 16.2 ft ridge vent requirement means 17 ft of vent (5 × 4 ft sections, with the spare foot cut off). Never round down — the code minimum is a minimum, and a shortfall on one side unbalances the system.
Frequently asked questions
How many soffit vents do I need?
It depends on the attic area and the ratio. A 2,000 sq ft attic at 1/300 needs 480 sq in of intake — 53.3 ft of continuous soffit vent (9 sq in per ft) or 10 individual soffit vents (50 sq in each). A 1,200 sq ft attic needs 32 ft of continuous soffit vent.
How much attic ventilation do I need?
By code (IRC R806.2): net free area of at least 1/150 of the attic floor area, or 1/300 with a vapour barrier. A 2,000 sq ft attic needs 960 sq in at 1/300 (480 exhaust + 480 intake) or 1,920 sq in at 1/150. Split it 50/50 between low intake and high exhaust.
What is net free area (NFA)?
NFA is the actual open area through a vent — the air can only pass through the louvres and screens, not the whole opening. A 12 × 12 in vent with a screen has about 72 sq in of NFA, not 144. Always use the manufacturer’s NFA rating, not the vent’s outside dimensions.
Do I need a ridge vent or box vents?
A ridge vent is better on most roofs: it runs the full ridge, so the exhaust is spread evenly and the intake/exhaust balance is easy to get right. Box vents are for roofs with no continuous ridge — hips, short ridges or complex roofs. A 2,000 sq ft attic needs 26.7 ft of ridge vent or 10 box vents.
Can you have too much attic ventilation?
Too much exhaust is a problem: if the exhaust NFA exceeds the intake NFA, the attic pulls conditioned air from the house through ceiling penetrations, raising energy bills. Too much intake is harmless. The rule is to keep the split 50/50 — never more exhaust than intake.